The EL9562 power supply terminal generates two electrically isolated output voltages from the 24 V DC input voltage. The output voltages can be tapped at the terminal with a current of 0.2 A. The power contacts are looped through. The power LEDs indicate the operating status of the terminal. An electrical isolation of 500 V exists between the input voltage and the output voltages. The two output voltages are also electrically isolated from each other. By connecting both voltages a symmetrical DC voltage can be generated.
Product status:
product announcement | estimated market release 2nd quarter 2024
Product information
Technical data | EL9562 |
---|---|
Technology | power supply terminal |
Short-circuit proof | yes |
Input voltage | 24 V DC (-15%/+20%) |
Output voltage | 24 V DC (-15%/+20%) |
Output current | 2 x ≤ 0,2 A |
Current consumption E-bus | 40 mA |
Insulation voltage | 1,500 V AC constant load field side/E-bus |
Insulation voltage input/output | 500 V AC permanent load (field side) |
Special features | automatic restart after short circuit, diagnostics UIN/UOUT |
Weight | approx. 55 g |
Operating/storage temperature | 0…+55°C/-25…+85°C |
Relative humidity | 95%, no condensation |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
Protect. rating/installation pos. | IP20/variable |
Approvals/markings | CE |
Housing data | EL-12-8pin |
---|---|
Design form | compact terminal housing with signal LEDs |
Material | polycarbonate |
Dimensions (W x H x D) | 12 mm x 100 mm x 68 mm |
Installation | on 35 mm DIN rail, conforming to EN 60715 with lock |
Side by side mounting by means of | double slot and key connection |
Marking | labeling of the BZxxx series |
Wiring | solid conductor (s), flexible conductor (st) and ferrule (f): spring actuation by screwdriver |
Connection cross-section | s*: 0.08…2.5 mm², st*: 0.08…2.5 mm², f*: 0.14…1.5 mm² |
Connection cross-section AWG | s*: AWG28…14, st*: AWG28…14, f*: AWG26…16 |
Stripping length | 8…9 mm |
Current load power contacts | Imax: 10 A |
*s: solid wire; st: stranded wire; f: with ferrule